GMV DC Inverter VRF 
52 
(3)  When debugging, the front panel of the outdoor unit must be completely closed, otherwise it 
will affect the accuracy of debugging (as shown in the Fig
.4.2.2
 as below). 
 
Fig.4.2.2 
(4)  Display instruction for each stage progress at the time of debugging:   
 
Instruction for each stage progress at the time of debugging 
— 
Progress code  Status code 
Meaning 
Progress 
Code 
Code 
Code 
01_set up 
master unit 
db  ON  01  ON  CC  ON 
The system hasn’t set master module. It 
needs to reset it. 
db  ON  01  ON  CF  ON 
The system has set more than 2 master 
modules. It needs to reset it. 
db  ON  01  ON  OC  ON 
Master module setting is succeeded. It will 
automatically enter into the next step. 
02_
a
llocate 
addresses 
db  ON  02  ON  Ad  Flash 
The system is conducting the address 
assignment. 
db  ON  02  ON  OC  ON 
Address assignment is succeeded. It will 
automatically enter into the next step. 
03_module 
quantity 
confirmation 
db  ON  03  ON  01~04  Flash 
LED3 displays the module quantity. It needs to 
manually confirm the module quantity. 
db  ON  03  ON  OC  ON 
Once the system module quantity is 
confirmed, it will automatically enter into the 
04_indoor 
unit quantity 
confirmation 
db  ON  04  ON 
quantity 
of online 
indoor 
Flash 
LED3 displays the quantity of online indoor 
units. 
db  ON  04  ON  OC  ON 
Indoor unit’s quantity inspection is finished. 
Enter into the next step automatically. 
05_detect 
internal 
communication
db  ON  05  ON  C2  ON 
The system has detected “communication 
malfunction between main control and inverter 
db  ON  05  ON  C3  ON 
The system has detected “communication 
malfunction between main control and inverter 
db  ON  05  ON  CH  ON 
Indoor/outdoor unit’s “rated capacity ratio is 
too high”. 
db  ON  05  ON  CL  ON 
Indoor/outdoor unit’s “rated capacity ratio is 
too low”. 
db  ON  05  ON  OC  ON 
System inspection is finished. Enter into the 
next step automatically.