Gree GMV6 DC Inverter VRF Units Service Manual
139
"HH" Over Voltage
Protection for the DC Bus
of Fan Drive
The fan drive boa rd is
abnormal
Yes
Whether th e i nput voltage of the unit
exceeds 460V?
No
Replace the fan drive board
Yes
Chang e the volta ge to
380V
2.89 "HL" Under Voltage Protection for DC Bus of Fan Drive
Fault display: main board of outdoor unit displays
Fault diagnosis:
If the fault code displayed on the 2-digit digital LED of the outdoor unit's main control board is HL, it
indicates the under voltage protection for the DC bus of fan drive.
Possible causes:
The unit's input power cable has a voltage below 320 V;
The fan drive board operates improperly.
Troubleshooting:
"HL" Under Vol tage
Protection for the DC Bus
of Fan Drive
The fan drive boa rd is
abnormal
Yes
Whether th e i nput voltage of the
unit falls below 320V?
No
Replace the fan drive board
Yes
Chang e the volta ge to
380V