Gree GMV6 DC Inverter VRF Units Service Manual
24
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
05_ detect internal
communication
db ON 05 ON C2 ON
The system has detected
“communication
malfunction between main
control and inverter
compressor driver”.
db ON 05 ON C3 ON
The system has detected
“communication
malfunction between main
control and inverter fan
driver”.
db ON 05 ON CH ON
Indoor/outdoor units’ rated
capacity ratio is too high.
db ON 05 ON CL ON
Indoor/outdoor units’ rated
capacity ratio is too low.
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 9:
The unit debugging step 06 is “outdoor unit’s parts inspection”.
If there is no abnormality in the detection, the display is below, and then it automatically enters the
next step of detection.
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
06_outdoor unit’s
parts inspection
db ON 06 ON OC ON
The system detected that
there’s no fault for outdoor
unit’s parts. Then it will
automatically enter into
the next step.
If an abnormality is detected, it will stay in the current state and manual troubleshooting is required.
The corresponding faults are as below:
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
06_outdoor unit’s
parts inspection
db ON 06 ON
Corresponding
error code
ON
The system detected that
there’s fault for outdoor
unit’s parts.
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 10:
The unit debugging step 07 is “indoor unit’s parts inspection”.
If there is no abnormality in the detection, the display is as below, and then it automatically enters
the next step of detection.

Other manuals for Gree GMV-560WM/G-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-560WM/G-X and is the answer not in the manual?

Gree GMV-560WM/G-X Specifications

General IconGeneral
BrandGree
ModelGMV-560WM/G-X
CategoryInverter
LanguageEnglish

Related product manuals