MULTI VRF- INDOOR UNIT SERVICE MANUAL EUROPEAN/LATIN AMETICA (R410A)
100
If the tightening torque for the flare nut is too great, leakage would happen.
3.11.4 Selection of air switch and power cord
Model
Power Cord
Size
Air Switch apacity
(A)
Minimum Sectional Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional Area of
Power Cord
(mm
2
/AWG)
GMV-N22G/A3A-K, GMV-
N22G/A2A-K
GMV-N22G/A4A-K, GMV-
N22G/A8A-K
GMV-N22G/C9A-K, GMV-
N22G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N28G/A3A-K, GMV-
N28G/A2A-K
GMV-N28G/A4A-K, GMV-
N28G/A8A-K
GMV-N28G/C9A-K, GMV-
N28G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N36G/A3A-K, GMV-
N36G/A2A-K
GMV-N36G/A4A-K, GMV-
N36G/A8A-K
GMV-N36G/C9A-K, GMV-
N36G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N45G/A3A-K, GMV-
N45G/A2A-K
GMV-N45G/A4A-K, GMV-
N45G/A8A-K
GMV-N45G/C9A-K, GMV-
N45G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N50G/A3A-K, GMV-
N50G/A2A-K
GMV-N50G/A4A-K, GMV-
N50G/A8A-K
GMV-N50G/C9A-K, GMV-
N50G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N56G/A3A-K, GMV-
N56G/A2A-K
GMV-N56G/A4A-K, GMV-
N56G/A8A-K
GMV-N56G/C9A-K, GMV-
N56G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N63G/A3A-K, GMV-
N63G/A2A-K
GMV-N63G/A4A-K, GMV-
N63G/A8A-K
GMV-N63G/C9A-K, GMV-
N63G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18
GMV-N71G/A3A-K, GMV-
N71G/A2A-K
GMV-N71G/A4A-K, GMV-
N71G/A8A-K
GMV-N71G/C9A-K, GMV-
N71G/E3A-K
220-240V
~ 50Hz
6
1.0/AWG18
1.0/AWG18

Table of Contents