MULTI VRF-Ⅱ  INDOOR UNIT SERVICE MANUAL    EUROPEAN/LATIN AMETICA (R410A) 
59 
In parameter query status, signals of the remote controller are invalid. 
5.1.6 Engineering Parameter Settings 
Engineering parameters can be set in power-on or power-off status. 
(1)  Press  and  hold  the  “FUNCTION”  button  for  five  seconds.  The  temperature  area  displays  “C00”. 
Continuously  press  the  “MODE”  button  for  three  times,  and  then  press  and  hold  the 
“FUNCTION” button for five seconds to enter the engineering parameter setting interface. The 
temperature area displays “P00”. 
(2)  Select a parameter code by pressing “ ” or “ ”. Press the “MODE” button to switch to parameter 
value settings. The parameter value blinks. Adjust the parameter value by pressing “ ” or “ ” and 
then press the “ENTER/CANCEL” button to complete settings. 
(3)  Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter settings. 
In the engineering parameter setting interface, users can also set user parameters listed in Table 3.2.   
The engineering parameter setting list is as follows: 
Table 2.4 Engineering Parameter Setting List 
00: standby after 
power-down recovery 
01: restoring the 
original status after 
power-down recovery 
Historical fault 
clearing for IDU 
Historical faults of all IDUs 
controlled by the current wired 
controller are cleared. 
Environment 
temperature 
sensor settings 
for IDU 
01: temperature sensor 
of air return vent 
02: temperature sensor 
of wired controller 
03: temperature sensor 
of air return vent for 
cooling, dehumidifying, 
and air supply; 
temperature sensor of 
wired controller for 
heating 
04: temperature sensor 
of wired controller for 
cooling, dehumidifying, 
and air supply; 
temperature sensor of 
air return vent for 
heating 
When there are master and slave 
wired controllers and the 
temperature sensor of wired 
controller is used, only the 
temperature sensor of the master 
wired controller is used by default. 
Note: 
1) In automatic mode, the 
environment temperature sensor 
settings are invalid for a common 
IDU but the setting value is 
memorized. 
2)The environment temperature 
sensor settings are invalid for a 
fresh-air IDU. The temperature 
sensor of air return vent is used by 
default. 
Corrected value 
of environment 
temperature 
sensor of IDU 
(for cooling, 
dehumidifying, 
and air supply) 
Temperature 
sensor of unit: 
0°C ; temperature 
sensor of wired 
controller: 0°C  
Press “ ” or “ ” to add or reduce 
by 1°C . 
Corrected value 
of environment 
temperature 
sensor of IDU 
(for heating, fast 
heating, and air 
warming) 
Temperature 
sensor of unit: -
2°C ; temperature 
sensor of wired 
controller: 0°C  
Press ” ” or ” ” to add or reduce 
by 1°C . 
The temperature sensor of unit and 
the temperature sensor of wired 
controller share the same corrected 
value. 
In heating mode, corrected value of 
temperature sensor of unit = 
corrected value of temperature 
sensor of wired controller - 2°C. 
Press " " or " " to add or reduce 
by 10%.