EasyManua.ls Logo

Gree GMV-PD140W/NAB-K

Gree GMV-PD140W/NAB-K
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
46
DC Inverter Multi
VRF Service Manual
DPOUSPM
Installation Table
Table 3 Installation Table
Region No. Indoor unit no. Present indoor unit no. Indoor unit location
08 03 08-03 No.3 indoor unit in Room B Floor A
Note:
1 ) Region no. indicates online region no.1-64, displayed by the centralized controller.
2 ) Indoor unit no. indicates online indoor unit no., 1-16, displayed by centralized controller.
3 ) Present indoor unit no. indicates present indoor unit no. displayed by centralized controller.
4 ) Indoor unit location indicates actual location of centralized controller, which is expressed by No.___
indoor unit, Room____, Floor ______.
7.2.8 Attachment
Error Code List:
Error code list of GMV VRF
Error Code Malfunction
E1 High pressure protection of compressor
E2 Antifreezing protection of indoor unit
E3 Low pressure protection of compressor
E4 Discharge temperature protection of compressor
E5 Overcurrent protection, overload protection of compressor, drive malfunction
E6 Communication malfunction
E7 0RGHVFRQÀLFW
E8 Indoor fan motor protection
E9 :DWHURYHUÀRZSURWHFWLRQFDVVHWWHW\SHXQLW
EH E-heater protection
F0 Ambient temperature sensor malfunction of indoor unit
F1 Malfunction of coil pipe inlet sensor of indoor unit
F2 Malfunction of coil pipe intermediate sensor of indoor unit
F3 Malfunction of coil pipe outlet sensor of indoor unit
F4 Ambient temperature sensor malfunction of outdoor unit
F5 Malfunction of coil pipe inlet sensor of outdoor unit
F6 Malfunction of coil pipe intermediate sensor of outdoor unit
F7 Malfunction of coil pipe outlet sensor of outdoor unit
F8 0DOIXQFWLRQRIGLVFKDUJHWHPSHUDWXUHVHQVRU¿[HG
F9 Malfunction of discharge temperature sensor 2 (digital)
FA 0DOIXQFWLRQRIRLOWHPSHUDWXUHVHQVRU¿[HG
Fb Malfunction of oil temperature sensor 2 (digital)
Fc High pressure sensor malfunction
Fd Low pressure sensor malfunction
H6 PG Motor Stalling Protection