4.1 Product Data
Model GMV-Pd100W/NaB-K GMV-Pd120W/NaB-K GMV-Pd140W/NaB-K GMV-Pd160W/NaB-K
Product Code CN850W0072 CN850W0012 CN850W0022 CN850W0032
Capacity
Cooling
a
kW 10 12 14 16
kBtu/h 34 41 48 55
Heating
b
kW 11 14 15.4 17.6
kBtu/h 38 48 53 60
Sound Pressure Level dB(A) 58 58 58 60
Refrigerant R410A R410A R410A R410A
Refrigerant Filling Amount kg 7.5 7.5 7.5 7.5
Power Supply V/Hz/Ph 220-240/50/1 220-240/50/1 220-240/50/1 220-240/50/1
Power input
Cooling kW 2.86 3.5 4.36 4.98
Heating kW 2.6 3.4 4.05 4.85
Current
Cooling A 14.20 17.30 20.50 23.20
Heating A 13.20 16.40 19.60 21.90
Circuit breaker A 40 40 40 40
Recommended Power Lines mm
2
×N 4×3 4×3 6×3 6×3
Compressor type
DC inverter dual-
rotor type
DC inverter dual-
rotor type
DC inverter dual-
rotor type
DC inverter dual-
rotor type
Moisture protection IP24 IP24 IP24 IP24
Climate Type T1 T1 T1 T1
Connection
Pipes
High pressure
Gas Pipe
mm////
High pressure
Gas Pipe
Inch / / / /
Low pressure
Gas Pipe
mm////
Low pressure
Gas Pipe
Inch / / / /
Liquid Pipe
mm ĭ ĭ ĭ ĭ
Inch 3/8 3/8 3/8 3/8
Connection Method Flare Connection Flare Connection Flare Connection Flare Connection
Dimensions
of Unit
Width mm 950 950 950 950
Depth mm 340 340 340 340
Height mm 1250 1250 1250 1250
Dimensions
of Package
Width mm 1110 1110 1110 1110
Depth mm 450 450 450 450
Height mm 1280 1280 1280 1280
Net Weight kg 111 111 111 115
Gross Weight kg 122 122 122 122
Loading Quantity
( 20’ Container )
a
unit 26 26 26 26
Loading Quantity
( 40’ Container )
b
unit 54 54 54 54
Loading Quantity ( 40’ High
Cube Container )
c
unit 54 54 54 54