98
DC Inverter Multi
VRF Service Manual
2 FLOW CHART OF TROUBLESHOOTING 
2.1 High-pressure Protection
High-pressure protection
Use pressure gauge to 
measure if the pressure is 
really high?
Check if the operation mode of 
indoor unit is set properly?
Check if the gas valve and 
liquid valve are fully open?
Check if the front panel of 
outdoor unit is covered tightly?
Check if the air inlet and
 outlet of the indoor and 
outdoor exchanger is 
smooth?
Check if the indoor and 
outdoor fans run normally?
Check if the indoor swing 
louver is fully open?
Check if the capacity output of 
outdoor unit is equal to the 
capacity demand of indoor 
units?
Check if the indoor electronic 
expansion valve can work 
normally
Check if the indoor / outdoor
filters or radiating fins are dirty 
or blocked?
The system pipe is blocked
Refer to the Repair and Maintenance
Engage the valve body with the coil
Refer to the dial-up of indoor and outdoor unit
Measure the swing motor and signal 
input
Measure the fan motor 
and signal input
Remove the obstructions
Cover up the front panel properly
Fully open the valve
Refer to the Instruction 
Manual for Indoor Unit
Measure if the pressure switch 
is normal˛
Replace the mainboard 
of outdoor unit
Replace the pressure switch
Yes
Focus on checking the inlet and outlet of the connection between indoor units 
and main pipe. Also focus on checking the electronic expansion valve of indoor
 unit and outdoor unit. Replace the electronic expansion valve, drying filter and 
other parts
No
No
No
No
No
No
No
No
No
YesNo
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No