VRF Service Manual
2.2 Low-pressure Protection
Low-pressure protection
Use pressure gauge 
to measure if the pressure 
is really low?
Check if the refrigerant
 in the system is too low?
Check if the operation 
mode of indoor unit is 
set properly?
Check if the gas valve
 and liquid valve of outdoor unit are 
fully open?
Check if the front panel 
of outdoor unit is 
covered tightly?
Check if the air inlet and 
outlet of the indoor and outdoor 
exchanger is smooth?
Check if the indoor and 
outdoor fans run 
normally?
Check if the indoor swing
 louver is fully open?
Check if the capacity output of 
outdoor unit is equal to the capacity 
demand of indoor units?
Check if the indoor electronic 
expansion valve can 
work normally
Check if the indoor / outdoor
filters or radiating fins are dirty or 
blocked?
The system pipe is blocked
Refer to the Repair 
and Maintenance
Engage the valve body 
with the coil
Refer to the dial-up of indoor 
and outdoor unit
Measure the swing 
motor and signal input
Measure the fan 
motor and signal input
Remove the obstructions
Cover up the front panel 
properly
Fully open the valve
Refer to the Instruction 
Manual for Indoor Unit
Refer to low pressure sensor 
error
Add refrigerant according to the nominal refrigerant volume 
on nameplate and the calculated charge volume
Focus on checking the inlet and outlet of the connection between
indoor units and main pipe. Also focus on checking the electronic 
expansion valve of indoor unit and outdoor unit. Replace the 
electronic expansion valve, drying filter and other parts
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes