8
Outdoor Units_Heat Recovery To n 12 14
Model - GMV-Q144WM/B1-F(U) GMV-Q168WM/B1-F(U)
Module combination - GMV-Q144WM/B1-F(U) GMV-Q168WM/B1-F(U)
Performance
Nominal Cooling Capacity
Btu/h 144000 168000
kW 42.20 49.24
Rated Cooling Capacity Btu/h 136000 150000
Nominal Heating Capacity
Btu/h 162000 189000
kW 47.48 55.39
Rated Heating Capacity Btu/h 150000 180000
Cooling Power Input kW 12.93 14.52
Heating Power Input kW 12.80 16.43
Sound Pressure Level dB(A) 64 65
Power Supply - 208/230V 3~ 60Hz
Compressor
Type - Inverter scroll type Inverter scroll type
Number N 2 2
Motor Output
kW 7.15+7.15 7.15+7.15
Starting Method - Inverter Inverter
Operating Range - 11%~100% 10%~100%
Refrigeration Oil Brand - FVC68D or FV-68H FVC68D or FV-68H
Oil Charge
Compressor L 1.1+1.1 1.1+1.1
Oil separate tank L 5 5
Total L 7.2 7.2
Fan
Type×Quantity - Propeller×2 Propeller×2
Motor output W 750+750 750+750
Starting method - Inverter Inverter
Air ow rate
m
3
/h 14000 16000
cfm 8240 9417
Max. external static pressure
Pa 82 82
in.W.G 0.328 0.328
Ambient
temperature
range
Cooling
°C -5~52 -5~52
23~125.6 23~125.6
Heating
°C -20~24 -20~24
-4~75.2 -4~75.2
Refrigerant
Refrigerant Type - R410A R410A
Refrigerant Charge Volume
kg 11.7 11.7
lbs. 25.79 25.79
Control - EXV EXV

Other manuals for Gree GMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Series and is the answer not in the manual?

Gree GMV5 Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Series
CategoryInverter
LanguageEnglish

Related product manuals