GMV5 HR HEAT RECOVERY
VRF Units Technical Sales Guide
Under the following conditions, the length can reach 90m(295-1/4feet).
1) Actual length of pipe in total: L1+L2x2+L3x2+L4x2+…+L9x2+a+b+…+i+j
1000m(3280-
3/4feet).
2) Length between each IDU and its nearest branch a, b, c, d, e, f, g, h, i, j
40m(131-1/4feet).
3) Difference between the pipe length from the first branch of IDU to the farthest IDU and the pipe
length from the first branch of IDU to the nearest IDU: L10-L11
40m(131-1/4feet).
(2) When the outdoor unit is at upper side and height difference is more than 50m, please consult
company for the related technical requirement.
(3) When the maximum length of the main pipe from ODU to the first branch of IDU is
90m(295-
1/4feet), then adjust the pipe size of the gas pipe and liquid pipe of main pipe according to the
following table.
Outdoor Model
Size of connection between outdoor unit and the rst indoor branch
Low pressure gas pipe mm(in.) Liquid pipe mm(in.) High pressure gas pipe mm(in.)
GMV-Q72WM/B-F(U) No need to enlarge pipe size No need to enlarge pipe size No need to enlarge pipe size
GMV-Q96WM/B-F(U) No need to enlarge pipe size
Ф
12.7(1/2)
Φ
22.2(7/8)
GMV-Q120WM/B-F(U) No need to enlarge pipe size
Ф
15.9(5/8)
Φ
28.6(1-1/8)
GMV-Q144WM/B1-F(U)
Ф
34.9(1-3/8)
Ф
15.9(5/8)
Φ
28.6(1-1/8)
GMV-Q144WM/B-F(U)
Ф
34.9(1-3/8)
Ф
15.9(5/8)
Φ
28.6(1-1/8)
GMV-Q168WM/B1-F(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4)
Φ
28.6(1-1/8)
GMV-Q168WM/B-F(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4)
Φ
28.6(1-1/8)
GMV-Q192WM/B-F(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4) No need to enlarge pipe size
GMV-Q216WM/B-F(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4) No need to enlarge pipe size
GMV-Q240WM/B-F(U) No need to enlarge pipe size
Ф
19.05(3/4)
Ф
34.9(1-3/8)
GMV-Q264WM/B-F(U) No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q288WM/B-F(U)
No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q312WM/B-F(U) No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q336WM/B-F(U) No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q360WM/B-F(U) No need to enlarge pipe size
Φ
22.2(7/8) No need to enlarge pipe size
GMV-Q72WM/B-U(U) No need to enlarge pipe size No need to enlarge pipe size No need to enlarge pipe size
GMV-Q96WM/B-U(U) No need to enlarge pipe size
Ф
12.7(1/2)
Φ
22.2(7/8)
GMV-Q120WM/B-U(U)
No need to enlarge pipe size
Ф
15.9(5/8)
Φ
28.6(1-1/8)
GMV-Q144WM/B-U(U)
Ф
34.9(1-3/8)
Ф
15.9(5/8)
Φ
28.6(1-1/8)
GMV-Q168WM/B-U(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4)
Φ
28.6(1-1/8)
GMV-Q192WM/B-U(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4) No need to enlarge pipe size
GMV-Q216WM/B-U(U)
Ф
34.9(1-3/8)
Ф
19.05(3/4) No need to enlarge pipe size
GMV-Q240WM/B-U(U)
No need to enlarge pipe size
Ф
19.05(3/4)
Ф
34.9(1-3/8)
GMV-Q264WM/B-U(U) No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q288WM/B-U(U) No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q312WM/B-U(U) No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q336WM/B-U(U)
No need to enlarge pipe size
Φ
22.2(7/8)
Ф
34.9(1-3/8)
GMV-Q360WM/B-U(U) No need to enlarge pipe size
Φ
22.2(7/8) No need to enlarge pipe size
(4) If the length between an IDU and its nearest branch is above 40m(131-1/4feet), then double the

Other manuals for Gree GMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Series and is the answer not in the manual?

Gree GMV5 Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Series
CategoryInverter
LanguageEnglish

Related product manuals