32
4
ELECTRICAL SPECIFICATIONS
Outdoor units
Power Supply Fuse Capacity
Minimum Circuit
Ampacity
Maximum Overcurrent
Protection
V/Ph/Hz A A A
GMV-Q72WM/B-F(U) 208V/230V 3~ 60Hz 35 32 35
GMV-Q96WM/B-F(U) 208V/230V 3~ 60Hz 45 37 45
GMV-Q120WM/B-F(U) 208V/230V 3~ 60Hz 60 50 60
GMV-Q144WM/B1-F(U) 208V/230V 3~ 60Hz 70 55 70
GMV-Q168WM/B1-F(U) 208V/230V 3~ 60Hz 70 57 70
GMV-Q144WM/B-F(U) 208V/230V 3~ 60Hz 35+35 32+32 35+35
GMV-Q168WM/B-F(U) 208V/230V 3~ 60Hz 35+45 32+37 35+45
GMV-Q192WM/B-F(U) 208V/230V 3~ 60Hz 45+45 37+37 45+45
GMV-Q216WM/B-F(U) 208V/230V 3~ 60Hz 45+60 37+50 45+60
GMV-Q240WM/B-F(U) 208V/230V 3~ 60Hz 60+60 50+50 60+60
GMV-Q264WM/B-F(U) 208V/230V 3~ 60Hz 35+45+45 32+37+37 35+45+45
GMV-Q288WM/B-F(U) 208V/230V 3~ 60Hz 45+45+45 37+37+37 45+45+45
GMV-Q312WM/B-F(U) 208V/230V 3~ 60Hz 45+45+60 37+37+50 45+45+60
GMV-Q336WM/B-F(U) 208V/230V 3~ 60Hz 45+60+60 37+50+50 45+60+60
GMV-Q360WM/B-F(U) 208V/230V 3~ 60Hz 60+60+60 50+50+50 60+60+60
GMV-Q72WM/B-U(U) 460V 3~ 60Hz 20 15 20
GMV-Q96WM/B-U(U) 460V 3~ 60Hz 25 18 25
GMV-Q120WM/B-U(U) 460V 3~ 60Hz 30 25 30
GMV-Q144WM/B-U(U) 460V 3~ 60Hz 20+20 15+15 20+20
GMV-Q168WM/B-U(U) 460V 3~ 60Hz 20+25 15+18 20+25
GMV-Q192WM/B-U(U) 460V 3~ 60Hz 25+25 18+18 25+25
GMV-Q216WM/B-U(U) 460V 3~ 60Hz 25+30 18+25 25+30
GMV-Q240WM/B-U(U) 460V 3~ 60Hz 30+30 25+25 30+30
GMV-Q264WM/B-U(U) 460V 3~ 60Hz 20+25+25 15+18+18 20+25+25
GMV-Q288WM/B-U(U) 460V 3~ 60Hz 25+25+25 18+18+18 25+25+25
GMV-Q312WM/B-U(U) 460V 3~ 60Hz 25+25+30 18+18+25 25+25+30
GMV-Q336WM/B-U(U) 460V 3~ 60Hz 25+30+30 18+25+25 25+30+30
GMV-Q360WM/B-U(U) 460V 3~ 60Hz 30+30+30 25+25+25 30+30+30