Air-to-water Heat Pump
9
MONOBLOC
TYPE
During repairs to sealed components, all electrical supplies shall be disconnected 
from the equipment being worked upon prior to any removal of sealed covers, etc. If 
it is absolutely necessary to have an electrical supply to equipment during servicing, 
then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.
Particular attention shall be paid to the following to ensure that by working on 
electrical components, the casing is not altered in such a way that the level of 
protection is affected. This shall include damage to cables, excessive number of 
connections, terminals not made to original specication, damage to seals, incorrect 
tting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer 
serve the purpose of preventing the ingress of ammable atmospheres. Replacement 
parts shall be in accordance with the manufacturer’s specications.
NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak 
detection equipment.
Intrinsically safe components do not have to be isolated prior to working on them.
Do not apply any permanent inductive or capacitance loads to the circuit without 
ensuring that this will not exceed the permissible voltage and current permitted for the 
equipment in use.
Intrinsically safe components are the only types that can be worked on while live in 
the presence of a ammable atmosphere. The test apparatus shall be at the correct 
rating.
Replace components only with parts specified by the manufacturer. Other parts 
may result in the ignition of refrigerant in the atmosphere from a leak.
Check that cabling will not be subject to wear, corrosion, excessive pressure, 
vibration, sharp edges or any other adverse environmental effects. The check shall 
also take into account the effects of ageing or continual vibration from sources such 
as compressors or fans.
Under no circumstances shall potential sources of ignition be used in the searching 
for or detection of refrigerant leaks. A halide torch (or any other detector using a naked 
ame) shall not be used.
Equipment shall be labelled stating that it has been de-commissioned and emptied 
of refrigerant. The label shall be dated and signed. Ensure that there are labels on the 
equipment stating the equipment contains ammable refrigerant