Air-to-water Heat Pump
30
MONOBLOC
TYPE
switch on (outdoor)temperature and control logic(1/2). 
   
14. Gate-controller
If there is gate control function, installation guide follow as:
220-240VAC
15. Charging and Discharging of Refrigerant
The unit has been charged with refrigerant before delivery. Overcharging or undercharging will cause the 
compressor to run improperly or be damaged. When refrigerant is required to be charged or discharged for 
installation, maintenance and other reasons, please follow steps below and nominal charged volume on the 
nameplate.
Discharging: remove metal sheets of the outer casing, connect a hose to the charging valve and then discharge 
refrigerant.
Charging 
valve 1
Charging 
valve 2
Notes
(a) Discharge is allowed unless the unit has been stopped. (Cut off the power and repower it 1 minutes later)
(b) Protective measures should be taken during discharging to avoid frost bites.
(c) When discharging is nished, if vacuuming cannot be done immediately, remove the hose to avoid air or 
foreign matters entering the unit.
(d) Vacuuming: when discharging is finished, use hoses to connect the charging valve, manometer and 
vacuum pump to vacuum the unit.