47
Technical Information
Service Manual
1. Frequency limited
If  [T
heating  overload  frequency-limited  temperature
]≤T
inner pipe
  <[T
heating  overload  frequency  reducing  temperature  at  normal  speed
]  ,  you  should  limit  the  frequency  raising  of 
compressor.
2. Reducing frequency at normal speed and stopping machine:
If T[
heating overload frequency  reducing temperature at  normal speed
]≤T
inner pipe
<[T
heating overload frequency  reducing temperature at  high speed
], you should adjust the compressor 
frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if T
 heating overload frequency reducing temperature at normal speed 
≤T
inner 
pipe
, then overload protects machine stopping;
3. Reducing frequency at high speed and power turn-off:
If [T
heating  overload  frequency  reducing  temperature  at  high  speed
]≤T
inner pipe
<[T
heating  overload  power  turn-off temperature
], you  should  adjust  the  compressor  frequency  by 
reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if T heating overload frequency reducing temperature at normal 
speed ≤T outer pipe, then Cooling overload protects machine stopping;
4. Power turn-off:
If the [T
heating overload power turn-off temperature
] ≤T
inner pipe
, then overload protects machine stopping; If T inner pipe T heating overload frequency-limited 
temperature and the compressor has been stopped working for 3 minutes, the machine should be allowed to operate.
5. If  the  overload protection power turn-off continuously occurs  for  six times, it should  not  be resumed automatically, and you should press 
the ON/OFF button to resume if the fault keeps on. During the process of running, if the running time of compressor exceeds the t overload 
protection times zero clearing time , the times of overload protection power turn-off should be cleared to recount. The mode of stopping the 
machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed, transferring mode will not clear 
it). Protective function for discharge temperature of compressor
1. Starting estimation:
After  the  compressor  stopped  working  for  180s,  if  T
Discharge
 <T
Discharge  limited  temperature
  (the  temperature  of  hysteresis  is  2ºC  ),  the  machine  is 
allowed to start, otherwise it should not be started, and should be stopped to treat according to the discharge temperature:
The  machine  should  be  stopped  or  transferred  to  supply  air,  the  trouble  should  be  cleared  immediately,  and  the  protection  times  are  not 
counted.
2. Frequency limited
If [T
Limited frequency  temperature during  discharging
] ≤T
Discharge
<[T
frequency reducing  temperature at  normal speed during  discharging
] , you should  limit the frequency  raising of 
compressor.
3. Reducing frequency at normal speed and stopping machine:
If [T
frequency reducing temperature at normal speed during discharging
] ≤T
Discharge
<[T
frequency reducing temperature at high speed during discharging
], you should adjust the compressor 
frequency by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [T
frequency reducing temperature at normal speed during discharging
] 
≤T
Discharge
, you should discharge to protect machine stopping;
4. Reducing frequency at high speed and power turn-off:
If [T
frequency reducing temperature at high speed during discharging
] ≤T
Discharge
 <[T
Stop temperature during discharging
], you should adjust
the compressor frequency by reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if [T
frequency reducing temperature at normal 
speed during discharging
] ≤T
Discharge
, you should discharge to protect machine stopping;
5. Power turn-off:
If the [T
Power turn-off temperature during discharging
] ≤T
Discharge
, you should discharge to protect machine stopping; If [T
Discharge
]<[T
Limited frequency temperature during 
discharging
] and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.
6. If the discharging temperature protection of compressor continuously occurs for six times, it should not be resumed automatically, and you 
should press the ON/OFF button to resume. During the process of running, if the running time of compressor exceeds the t Protection times 
clearing of  discharge , the  discharge protection is  cleared to recount.  Stopped or transferred to supply air mode  will clear the  trouble times 
immediately (if the trouble can not be resumed, mode transferring also will not clear it).
7. Frequency limited
If [I
Limited frequency when overcurrent
] ≤I
AC Electric current
 <[I
 frequency reducing when overcurrent
], you should limit the frequency raising of compressor.
8. Reducing frequency:
If [I
Frequency reducing when overcurrent
] ≤[I
AC Electric current I Power turn-off when overcurrent
] , you should reduce the compressor frequency till the lower limit or exit 
the frequency reducing condition;
9. Power turn-off:
If [I
Power turn-off machine when overcurrent
] ≤[I
AC Electric current
] , you should carry out the overcurrent stopping protection; If I 
AC Electric current
<[T
 Limited frequency when 
overcurrent
] and the compressor has been stopped for 3 minutes, the machine should be allowed to operate.
10. If the overcurrent protection continuously occurs for six times, it should not be resumed automatically, and you should press the ON/OFF 
button to  resume.  During  the  process of  running,  if  the  running time  of  compressor  exceeds  the  [t
 Protection  times  clearing  of  over  current
] ,  the  discharge 
protection is cleared to recount.