71
Installation and Maintenance
Service Manual
38
Zero-crossing 
malfunction of 
outdoor unit
U9
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
Hardware malfunction 
of outdoor units main 
board;
1. Replace outdoor units 
main board AP1;
39
Limit/decrease 
frequency due to 
freeze protection
FH
All loads operates normally, 
while operation frequency of 
compressor decreases. 
Poor air return of 
indoor unit or speed of 
fan is too low
1. Check whether indoor 
units horizontal louver 
can close normally → 
replace indoor units main 
board → replace indoor 
units motor; 
9.2 Troubleshooting for Main Malfunction
Indoor unit:
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● 
Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● 
Is there short circuit due to trip-over of the parts?
● 
Is the temperature sensor broken?
● 
Is mainboard  broken?
Malfunction diagnosis process:
Is the wiring terminal between the 
temperature sensor and the controller 
loosened or poorly contacted?
Start
Insert the temperature 
sensor tightly
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Is malfunction 
eliminated
Is malfunction 
eliminated
Is malfunction 
eliminated
Replace it with a 
temperature sensor with 
the same model
Make the parts upright
Is there short circuit due to trip-
over of the parts
Is the temperature sensor normal 
according to the resistance table?
Replace the mainboard with 
the same model.
End