3. High temperature and overload protection (E8)(AP1 below means control board of outdoor unit)
Main detection points:
●
 If the outdoor ambient temperature is in normal range;
● 
If the indoor and outdoor fan are running normally;
● 
If the radiating environment of indoor and outdoor unit is good.
Malfunction diagnosis process:
Y
N
Y
Y
N
N
Y
Y
Y
Y
Y
Y
N
N
N
E8 is displayed
              If the outdoor 
ambient temperature is higher
              than 53℃?
Normal protection, please 
use it after improving the 
outdoor ambient temperature
Unit restarts 
   normally
Unit restarts 
   normally
If the radiating of indoor 
and outdoor unit is good?
Improve the radiating environment 
of unit (clean the heat exchanger 
and remove surrounding obstacles)
If the indoor and outdoor 
fan are running normally?
Connect normally?
Adjust the 
connection
Replace outdoor 
mainboard
Replace mainboard
Replace Motor
Replace Fan 
   capacitor
Fan capacitor is broken?
Motor is broken?
End