46
Technical Information
Service Manual
1. Starting estimation:
After  the  compressor  stopped  working  for  180s,  if  T
inner pipe
>  [T
frozen-preventing  frequency-limited  temperature
  (the  temperature  of  hysteresis  is  2  )],  the 
machine is only allowed to start  for  operating,  otherwise  it  should  not  be  started,  and  should  be  stopped  to treat according to the frozen-
preventing protection: Clear the trouble under the mode of power turn-off / heating, and the protection times are not counted.
2. Frequency limited
[T
frozen-preventing  normal  speed  frequency-reducing  temperature
]  ≤[T
inner  pipe T  frozen-preventing  frequency-limited  temperature
]  ,  you  should  limit  the  frequency  raising  of 
compressor.
3. Reducing frequency at normal speed:
If  [T
frozen-preventing  high  speed  frequency-reducing  temperature
]  ≤[T
inner  pipe T frozen-preventing  normal  speed  frequency-reducing  temperature
],  you  should  adjust  the  compressor 
frequency by reducing 8Hz/90s till the lower limit;
4. Reducing frequency at high speed:
If [T
frozen-preventing power  turn-off temperature
] ≤T
 inner pipe
 [T
frozen-preventing high  speed frequency-reducing  temperature
] you  should adjust the  compressor frequency by 
reducing 30Hz/90s till the lower limit;
5. Power turn-off:
If the T
inner pipe
 <[T
frozen-preventing power turn-off temperature
], then frozen-preventing protect to stop the machine; If T[
frozen-preventing frequency-limited temperature
] 
<T
inner pipe
 , and the compressor has stopped working for 3 minutes, the whole machine should be allowed to operate.
6. If the frozen-preventing protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should 
press the  ON/OFF button to resume  if  the fault keeps  on.  During the process  of  running, if the  running  time of compressor exceeds  the t 
evaporator frozen-preventing protection times zero clearing time , the times of frozen-preventing power turn-off should be cleared to recount. 
The mode of stopping the machine or transferring to supply air will clear the trouble times immediately (if the trouble can not be resumed, 
mode transferring will not clear it).
(5) Overload protection function
Overload protection function at the mode of cooling and dehumidifying
1. Starting estimation:
After the compressor stopped working for 180s, if T
outer pipe
 <[T
Cooling overload frequency-limited temperature
] (the temperature of hysteresis is 2ºC ), the 
machine is allowed to start, otherwise it should not be started, and should be stopped to treat according to the overload protection: Clear the 
trouble at the mode of power turn-off / heating, and the protection times are not counted.
2. Frequency limited
If  [T
Cooling  overload  frequency-limited  temperature
]  ≤T
outer  pipe 
[T
Cooling  overload  frequency  reducing  temperature  at  normal  speed
],  you  should  limit  the  frequency  raising  of 
compressor.
3. Reducing frequency at normal speed and power turn-off:
If [T
Cooling overload frequency  reducing temperature at high speed
] ≤T
outer pipe
< [T
Cooling overload power  turn-off temperature
] , you should adjust the compressor frequency 
by reducing 8Hz/90s till the lower limit; After it was running 90s at the lower limit, if [T
Cooling overload frequency reducing temperature at normal speed
]≤T
outer pipe
, 
then Cooling overload protects machine stopping;
4. Reducing frequency at high speed and stop machine:
If [T
Cooling overload frequency reducing  temperature at high speed
]≤T
outer pipe
 [T
Cooling overload power turn-off temperature
], you should adjust the compressor frequency by 
reducing 30Hz/90s till the lower limit; After it was running 90s at the lower limit, if [T
Cooling overload frequency reducing temperature at normal speed
] ≤[T
outer pipe
], 
then Cooling overload protects machine stopping;
5. Power turn-off:
If the  [T
Cooling overload  power  turn-off temperature
] ≤T
outer pipe
, then Cooling  overload  protects  machine  stopping; If [T
outer pipe
]<[T
Cooling overload  frequency-limited 
temperature
]and the compressor has been stopped working for 3 minutes, the machine should be allowed to operate.
6. If the Cooling overload protection power turn-off continuously occurs for six times, it should not be resumed automatically, and you should 
press the  ON/OFF button to resume  if  the fault keeps  on.  During the process  of  running, if the  running  time of compressor exceeds  the t 
overload  protection  times  zero  clearing  time  ,  the  times  of  overload  protection  power  turn-off  should  be  cleared  to  recount.  The  mode  of 
stopping the  machine  or  transferring  to  supply  air  will  clear the  trouble  times  immediately  (if  the  trouble  can  not be  resumed,  transferring 
mode will not clear it).
Overload protection function at the mode of heating
Starting estimation :
After  the  compressor  stopped  working  for  180s,  if T inner  pipe T  heating  overload  frequency-limited  temperature  (the  temperature  of 
hysteresis is 2 ), the machine is allowed to start, otherwise it should not be started, and should be stopped to treat according to the overload 
protection:
Clear the trouble at the mode of power turn-off / heating, and the protection times are not counted.