70
Installation and Maintenance
Service Manual
38
Zero-crossing 
malfunction of 
outdoor unit
U9
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
Hardware malfunction 
of outdoor units main 
board;
1. Replace outdoor units 
main board AP1;
39
Limit/decrease 
frequency due to 
freeze protection
FH
All loads operates normally, 
while operation frequency of 
compressor decreases. 
Poor air return of 
indoor unit or speed of 
fan is too low
1. Check whether indoor 
units horizontal louver 
can close normally → 
replace indoor units main 
board → replace indoor 
units motor; 
●Discharging method
(1) remove the inverter cover(Outdoor Unit)
 
(2)As shown below,connect the discharge resistance(approx.100Ω20W)or plug of the sold ering iron to voltage between + - terminals of 
the electrolytic capacitor on PC Board for 30s, and then peformedischarging.
NOTE:
A  large-capacity  electrolytic  capacitor  is  used  in  the  outdoor  unit  controller(inverter).Therefore,if  the  power  supply  is  turned 
off,charge(charging voltage DC280V to 380V)remains and disc harging takes a lot of time.. After turning off the power source,if touching 
the charging section before discharging, an electrical shock may be caused. Discharge the electrol ytic capacitor completely by using 
soldering iron,etc.
P.C.board
(Soldered surface)
Inverter cover