69
Installation and Maintenance
Service Manual
34
Drop 
malfunction 
of DC busbar 
voltage
U3
Flash 
20 times 
every 3s
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
Power voltage 
is unstable, big 
uctuation.
1. Check whether 
power supply network is 
abnormal;
35
Low voltage 
protection of DC 
bus bar
PL
Flash 
21 times 
every 3s
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
The voltage at 
positions L and N on 
wiring board (XT) is 
lower than 150 VAC
1. Check whether 
power supply network is 
abnormal;
Hardware malfunction 
of outdoor units main 
board;
2. Replace outdoor units 
main board AP1;
36
Limit/decrease 
frequency due 
to module 
temperature 
protection
EU
All loads operates normally, 
while operation frequency of 
compressor decreases. 
Radiating grease on 
IPM module of outdoor 
units main board is not 
enough; screws havent 
been xed tightly; 
1. After the system is de-
energized for 20min and 
discharge, check whether 
radiating grease on IPM 
Module of outdoor control 
board AP1 is enough and 
whether the radiating is 
xed tightly; 
Hardware malfunction 
of outdoor units main 
board;
2. Replace outdoor units 
main board AP1;
37
4-way valve is 
abnormal
U7
This malfunction occurs 
under heating operation: all 
loads stop. 
Power voltage is lower 
than AC175V
Wiring terminal 4V is 
loose or broken
2. After de-energization, 
insert OVC-COMP tightly 
or replace wiring
Hardware malfunction 
of outdoor units main 
board;
3. Replace outdoor units 
main board AP1;