68
Installation and Maintenance
Service Manual
30
malfunction of 
read EEPROM
EE
Flash 
15 times 
every 3s
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
Wrong match between 
indoor unit and outdoor 
unit;
1. Check whether the 
capacity of indoor unit 
and outdoor unit is 
matching with each 
other; 
Hardware malfunction 
of indoor units main 
board;
2. Replace indoor units 
main board AP2;
Hardware malfunction 
of outdoor units main 
board;
3. Replace outdoor 
units main board AP1;
31
Charging 
malfunction of 
capacitor
PU
Flash 
17 times 
every 3s
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
See 9.3 (diagnosis of 
charging malfunction 
for capacitor)
Refer to maintenance 
owchart
32
Circuit 
malfunction 
of module 
temperature 
sensor
P7
Flash 
18 times 
every 3s
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
Hardware malfunction 
of outdoor units main 
board;
1. Replace outdoor 
units main board AP1;
33
Module 
temperature 
protection
P8
Flash 
19 times 
every 3s
During cooling and drying 
operation, compressor and 
outdoor fan stop while indoor 
fan operates. During heating 
operation, all loads stop.
Radiating grease on 
IPM module of outdoor 
units main board is not 
enough; screws havent 
been xed tightly; 
1. After the system is 
de-energized for 20min 
and discharge, check 
whether radiating 
grease on IPM Module 
of outdoor control board 
AP1 is enough and 
whether the radiating is 
xed tightly; 
Hardware malfunction 
of outdoor units main 
board;
2. Replace outdoor 
units main board AP1;