76
Installation and Maintenance
Service Manual
2. IPM protection(H5), desynchronizing malfunction(H7), overcurrent of compressor phase current (P5) (AP1 below means 
control board of outdoor unit)
Main detection points:
● 
Is voltage input within the normal range
● 
If the control board AP1 is well connected with compressor COMP? If they are loosened? If the connection sequence is correct?
● 
Heat exchange of unit is not good (heat exchanger is dirty and unit radiating environment is bad);
● 
If the system pressure is too high?
● 
If the refrigerant charging amount is appropriate?
● 
If coil resistance of compressor is normal? Is compressor coil insulating to copper pipe well?
● 
If the work load of unit is heavy? If radiating of unit is good?
Malfunction diagnosis process: