75
Installation and Maintenance
Service Manual
Outdoor unit:
1. Capacity charging malfunction (outdoor unit malfunction) (AP1 below means control board of outdoor unit)
Main detection points:
● 
Detect if the voltage of L and N terminal of XT wiring board is between 210VAC-240VAC by alternating voltage meter;
● 
Is reactor (L) well connected? Is connection wire loosened or pulled out? Is reactor (L) damaged?
Malfunction diagnosis process:
N
Y
N
Y
N
Y
N
Y
N
Y
Turn on the unit and 
wait 1 minute
Use AC voltmeter to measure 
the voltage on the two ends 
of electrolytic capacitor 
(see fig 30)
Voltage higher 
than 200V?
Malfunction of 
the outdoor 
mainboard AP1
Replace outdoor 
mainboard
Measure the voltage 
input with AC voltmeter
(see fig 30)
Voltage within 
180VAC~260VAC?
Shut down the power and wait 20 
minutes; or use DC voltmeter to 
measure the voltage on the two 
ends of electrolytic capacitor 
until the voltage is lower than 20V
Check the connection 
of reactor and connection 
wire
If the wiring of 
reactor L is normal?
Replace outdoor 
mainboard AP1
End
Power supply is 
abnormal; repair 
the power supply 
to restore the range 
between 180VAC
~260VAC
Power on and 
restart the unit
Is the Vmalfunction 
     eliminated?
Is the Vmalfunction 
     eliminated?
Connect the 
connection 
wire of reactor 
L correctly
Power on and 
restart the unit