23
Condensing Unit
Service Manual
Dry Clean Air tight
Make syre there is no
moisture inside the pipes
Make sure there is no
dirt inside the pipe
Make sure the refrigerant
does not leak out
Moisture
(V0965)
Dirt
(V1148)
Leak
(V1149)
Figure 3-1-1

Align copper pipe are with the center of screwed connector and tighten fully the nut of the are by hand.

Tighten the are nut with a torque spanner until the torque spanner makes a click, as shown in Figure 3-1-
1. Moment needed for tightening a nut is shown in Tab. 3-1-1.
Fitting Pipe for Indoor Unit Flaring Nuts Fitting pipe
Torque Spanner
Spanner
Figure 3-1-2
Form 3-1-1 the tightening torque needed for tightening nut
Pipe diameter Tightening torque
1/4" 15-30 (N·m)
3/8" 35-40 (N·m)
5/8" 60-65 (N·m)
1/2" 45-50 (N·m)
3/4" 1-75 (N·m)
7/8" 85-90 (N·m)

Curvature of piping shall not be too small, or otherwise piping may be broken. So installation personnel
should use a pipe bender to bend pipes.

Upward or longitudinal welding joint method is usually applied to the welding of pipelines. The welding
method that mouth of pipe is downward (face-down welding) should be avoided as far as possible,
because such method is prone to welding defects and even would cause leakage, as shown in Figure 3-1-
3.