Modbus Gateway(Pro)
16
6.2.3 Setting of Communication Connection
1 2
BMS
ONON
1 2
SA8
ONON
Modbus Gateway(Pro) 1
Master
ODU
Slave
ODU
Modbus Gateway(Pro) 2
Slave
ODU
Master
ODU
SA8
(1) Communication wire connection between Modbus Gateway(Pro) and BMS:
Step 1: Confirm the first Modbus Gateway(Pro) (Modbus Gateway(Pro)1 as
shown in the figure) that needs to be connected to BMS. Connect the R+ and R-
port of RS485-1 communication interface of this gateway and the BMS with
communication cable, as shown in step in the figure.
Step 2: Connect the R+ and R- port of RS485-1 communication interface of M
odbus Gateway(Pro)(Modbus Gateway(Pro)1) and the R+ and R- port of RS485-1
communication interface of the second Modbus Gateway(Pro)(Modbus Gateway(Pr
o)2 as shown in the figure) with communication cable, as shown in step in the fi
gure. If several Modbus Gateways(Pro) shall be connected, please connect them in
this way.