BACnet Gateway Kit for Central Air Conditioners
25
MS/TP slaves and certain other devices.) □Yes ■ No
2.8 Networking Options:
Router, Clause 6 - List all routing congurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP,
etc�
Appendix H, BACnet Tunneling Router over IP
□ BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices? □ Yes ■ No
2.9 Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported
simultaneously
ANSI X3.4 □ IBM™/Microsoft™ DBCS □ ISO 8859-1
□ ISO 10646 (UCS-2) □ ISO 10646 (UCS-4) □ JIS C 6226
3 BACnet Objects List
3.1 Supported BACnet Object Type
Based on the object type specified in the BACnet standard document, the object type and
name related to the air conditioning unit are listed as follows:
Object
number
Object Type
Hexadecimal
format
Decimal
format
Air conditioner Parameter name
0 Analog Input X’0000 0000’ 0
Indoor unit environment Temp,
Water tank temp(status), Double-
Tube supply Water Temp, Outdoor
environment temp
1 Analog Output X’0040 0000’ 4194304
2 Analog Value X’0080 0000’ 8388608
Indoor unit Temp(setting), Water tank
temp(setting), Floor Heating supply
Water Setting Temp.
3 Binary Input X’00C0 0000’ 12582912
Indoor unit general error mark, On/
Off(status), Specific error mark for
the GMV Water Heater, Disinfecting,
Floor heat power, Outdoor unit
general error mark , Complete
machine compressor state
4 Binary Output X’0100 0000’ 16777216 On/Off(setting)
5 Binary Value X’0140 0000’ 20971520
Swing(setting), Energy
saving(setting), Remote temp shield
mark(setting), Remote mode shield
mark(setting), Remote On/Off shield
mark(setting), Remote lock mark(all
shield)(setting)
6 Calendar X’0180 0000’ 25165824
7 Command X’01C0 0000’ 29360128