EasyManua.ls Logo

Gree MG30-24/D1(B) - Page 55

Gree MG30-24/D1(B)
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BACnet Gateway Kit for Central Air Conditioners
39
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the temperature setting of the water tank of the GMV
water heater.
Present_Value:
.
Hot Water, Night, Reserve modes:35 ~58 (the upper limit can be adjusted to 65 );
.
Energy saving mode:35 ~50 ;
.
High temp sterilization mode:65 ~70 ;
Units: degrees-Celsius or
Notes:
1) The temperature status of the water tank varies as the change of the running mode of the
water tank. This object name is WaterTankModeStatus_XX_YYY_ZZ.
2) This parameter is only for the GMV water heater.
(21) Water tank temp(setting)
Member number :20
Object name:WaterTankTempCommand_XX_YYY_ZZ (XX means Air condition type, like
GMV is 01;YYY means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means
Indoor Unit's number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's
Parameters.)
Object type:Analog Value
Object ID: AV(2)+YYY*8192+ZZ*64+1
Instance Number: YYY*8192+ZZ*64+1
Description: this object is used to monitor the temperature setting of the water tank of the GMV
heater water.
Present_Value:
.
Hot Water, Night, Reserve modes:35 ~58 (the upper limit can be adjusted to 65 );
.
Energy saving mode:35 ~50 ;
.
High temp sterilization mode:65 ~70 ;
Units: degrees-Celsius or
Notes:
1) The temperature setting range of the water tank varies as the change of the running mode of
the water tank whose object name is WaterTankModeStatus_XX_YYY_ZZ.
2) This parameter is only for the GMV water heater.
(22) Water tank(status)
Member number :21
Object name:WaterTankStatus_XX_YYY_ZZ (XX means Air condition type, like GMV is 01;YYY
means Outdoor Unit's number, like GMV is between 001 and 004 now; ZZ means Indoor Unit's
number, like GMV is between 01 and 16 now, otherwise 00 means device YYY's Parameters.)
Object type: Multistate Input
Object ID: MI(13)+YYY*8192+ZZ*64+2
Instance Number: YYY*8192+ZZ*64+2
Description: this object is used to monitor the status of the water tank of GMV water heater.
Present_Value:

Related product manuals