AIR-TO-WATER HEAT PUMP PRODUCT
7
4.1.2 Indoor
INDOOR UNIT
Model
GRS-CQ
6.0Pd/Na
-K(I)
GRS-CQ
8.0Pd/Na
-K(I)
GRS-CQ
10Pd/Na
-K(I)
GRS-CQ
12Pd/Na
-K(I)
GRS-CQ
14Pd/Na
-K(I)
Power Supply
V /
Ph /Hz
220240V/1Ph/50Hz
Rated input (indoor only)
W 3200 6200
Liquid side diameter
mm
(inch)
6.35(1/4)
9.52(3/8)
Gas side diameter
mm
(inch)
12.7(1/2)
15.9(5/8)
Cooling (FCU) 7-25
Cooling (Floor ) 18-25
Heating (FCU) 25-55(High Temperature Cycle)
Operation
Range(Outflow
water temp.)
Heating (Floor ) 25-45 (Low Temperature Cycle)
Type - Water-cooled
Nr. of speed - 3
Power input W 200
pump
Water flow
limit
LPM 7.5
Volume Liter 10
Water Pressure
(Max)
Bar 3
Expansion
Vessel
Water Pressure
(Pre)
Bar 1
Type - Sheath
Material - Stainless Steel
Operation - Automatic
Steps - 2
Capacity
Combination
KW 1.5+1.5 3+3
Electric
Heater
Power input
Ph/V/
Hz
1/230/50
Type - Brazed Plate HEX
Main components
Heat
Exchanger
Quantity - 1
Unit(W×D× H) mm
900×500×324
Dimensions
Packed unit(W×D× H) mm
1040×605×380