AIR-TO-WATER HEAT PUMP CONTROL
31
leaving water temperature (solar kit is installed)
③ Room temperature setting is available when you have selected room temperature
as control target.
④ Please refer function code 01.
⑤ In heating mode, if weather depending mode is activated, you can’t set the room
temperature or outflow water temperature.
⑥ In heating mode , there are two Heating operation level:
¾ high temperature cycle
¾ low temperature cycle
⑦ Please refer to In function code 19 ;
3) Adjust desired temperature by pressing
button.
Note:
①
: Increase 1°C or 1°F for each press.
②
: Decrease 1°C or 1°F for each press.
4) Press
button to save the setting target temperature and return to the main
menu.
The range of the setting temperature (unit:
℃)
Temperature Mode Temperature range
Outflow water temperature(NO FCU)
cool 18~25(default:18)
Outflow water temperature(FCU)
cool 7~25(default:7)
high temperature cycle 25~55(default:40)
Outflow water temperature Heat
low temperature cycle 25-45(default:40)
Room temperature cool 18~30(default:20)
Room temperature heat 18~30(default:26)
Sanitary water tank temperature / 40~80(default:50)