U-Match Series DC Inverter Service Manual
11
3.2 Operation Range
Mode
Range of Outdoor Temperature
Cooling
-15-48
Heating
-10-24
3.3 Electrical Data
3.3.1 Outdoor unit
Table 1-4-1 Electrical Data of Outdoor Unit
Model
Compressor
Fan Motor
Fuse/Breaker
Capacity
Min.
Power
Supply
Cord
Power Supply
Qty.
RLA
FLA
V/Ph/Hz
A
A
A
mm
2
GUHD24NS3GO
220-240,1,50/60
1
11.5
-
20
2.5
GUHD36NS3GO
220-240,1,50/60
1
19.0
-
20
4.0
GUHD42NS3GO
220-240,1,50/60
1
21.0
-
25
4.0
GUHD48NS3GO
220-240,1,50/60
1
21.0
-
40
6.0
GUHD60NS3GO
220-240,1,50/60
1
21.0
-
40
6.0
3.3.2 Indoor unit
Table 1-4-2 Electrical Data of Indoor Unit
Model
Power Supply
Fan Motor FLA
Fuse/Breaker
Capacity
Min. Power
Supply Cord
V/Ph/Hz
A
A
mm
2
GFH24S3GI
220-240,1,50/60
1
5/6
1.0
GFH24S3G1I
220-240,1,50/60
1
5/6
1.0
GFH36S3GI
220-240,1,50/60
1
5/6
1.0
GFH36S3G1I
220-240,1,50/60
1
5/6
1.0
GFH42S3GI
220-240,1,50/60
1
5/6
1.0
GFH42S3G1I
220-240,1,50/60
1
5/6
1.0
GFH48S3GI
220-240,1,50/60
1
5/6
1.0
GFH48S3G1I
220-240,1,50/60
1
5/6
1.0
GFH60S3GI
220-240,1,50/60
1
5/6
1.0
GFH60S3G1I
220-240,1,50/60
1
5/6
1.0
GKH24S3GI
220-240,1,50/60
1
5/6
1.0
GKH36S3GI
220-240,1,50/60
1
5/6
1.0
GKH42S3GI
220-240,1,50/60
1
5/6
1.0
GKH48S3GI
220-240,1,50/60
1
5/6
1.0
Notes:
RLA: Rated load amperes
LRA: Locked rotor amperes
FLA: Full load current
. Install the disconnect device with a contact gap of at least 3mm in all poles nearby the units
(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is
accessible.