U-Match Series DC Inverter Service Manual
74
3.2 Specification of Connection Pipe
3.2.1 Duct Type
Table 3-2-4
Item
Model
Size of Fitting
Pipe (inch)
Max. Pipe
Length (m)
Max. Height Difference
between Indoor Unit
and Outdoor Unit (m)
Drainage pipe(Outer
Diameter × wall
thickness) (mm)
Liquid
Gas
GFH24S3GI
GFH24S3G1I
GUHD24NS3GO
3/8
5/8
50
15
Ф20×1.2
GFH36S3GI
GFH36S31I
GUHD36NS3GO
3/8
5/8
50
15
Ф20×1.2
GFH42S3GI
GFH42S3G1I
GUHD42NS3GO
3/8
5/8
50
30
Ф20×1.2
GFH48S3GI
GFH48S3G1I
GUHD48NS3GO
3/8
5/8
50
30
Ф20×1.2
GFH60S3GI
GFH60S3G1I
GUHD60NS3GO
3/8
3/4
50
30
Ф31.5
3.2.2 Cassette Type
Table 3-2-4
Item
Model
Size of Fitting
Pipe (inch)
Max. Pipe
Length (m)
Max. Height
Difference between
Indoor Unit and
Outdoor Unit (m)
Drainage pipe(Outer
Diameter × wall
thickness) (mm)
Liquid
Gas
GKH24S3GI
GUHD24NS3GO
3/8
5/8
50
15
Ф31.2.3
GKH36S3GI
GUHD36NS3GO
15
Ф31.2.3
GKH42S3GI
GUHD42NS3GO
30
Ф31.2.3
GKH48S3GI
GUHD48NS3GO
30
Ф31.2.3
The connection pipe should be insulated with proper water-proof insulating material.
The pipe wall thickness shall be 0.5-1.0 mm and the pipe wall shall be able to withstand the
pressure of 6.0 MPa. The longer the connecting pipe, the lower the cooling and heating effect performs.
4 ELECTRIC WIRING WORK
4.1 Wiring Precautions
WARNING
. Before obtaining access to terminals, all supply circuits must be disconnected.
. The rated voltage of the unit is as shown as Table 1-4-1 and Table 1-4-2
. Before turning on, verify that the voltage is within the 198~264V range (for single phrase unit) .
. Always use a special branch circuit and install a special receptacle to supply power to the air conditioner.
. Use a special branch circuit breaker and receptacle matched to the capacity of the air conditioner.
. The special branch circuit breaker is installed in the permanent wiring. Always use a circuit that can trip all the
poles of the wiring and has an isolation distance of at least 3 mm between the contacts of each pole.
. Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively.
. Install a leakage special branch circuit breaker in accordance with the related laws and regulations and electric
company standards.