U-Match Series DC Inverter Service Manual
41
address of wired controller is set to match the address of long-distance control. The unit will memorize
this setting status. The setting value will be memorized after power failure. The detailed setting is as
shown in the Figure below:
Figure 2-7-10
2) Address setting of each unit: when the address mode is set to be long-distance control address
mode. The address setting value range is 01~255. The setting method is:
Under off state of the unit, press Function and Mode buttons at the same time for 5s to enter setting
interface of wired controller address. LCD displays address sequence. Press ▲ or button to adjust the
address sequence and then press Enter/Cancel button to confirm. The setting value will be memorized
after power failure. The detailed setting is as shown in the Figure below: