U-Match Series DC Inverter Service Manual
57
Ceiling
Hoisting stand
Clamp(attachment)
Drain hose(attachment)
Drain raising
hose
≤300mm(11-3/4inch)
1000~1500mm(39-3/8~59inch)
≤100mm
(39-3/8inch)
Figure 3-1-14
a. The vertical height of the drain hose should be 75mm or less so that it is unnecessary for the
drain port to withstand additional force.
Drain hose(attachment)
≤75mm(3inch)
≤1000mm
(39-3/8inch)
Figure 3-1-15
b. When multiple drain hoses are used, their installation should be performed as shown in the
figure below.
0~1000mm(0~39-3/8inch)
≥100mm(3-7/8inch)
T-joint converging drain pipes
T-joint converging drain pipes
Figure 3-1-16