EasyManua.ls Logo

Gree U-match Series

Gree U-match Series
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
U-Match Series DC Inverter Service Manual
76
WARNING
. Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
. Match the terminal block numbers and connection cord colors with those of the indoor unit side.
. Erroneous wiring may cause burning of the electric parts.
. Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
. Always fasten the outside covering of the connection cord with cord clamps. (If the insulator is not clamped,
electricleakage may occur.)
. Always connect the ground wire.
(4) Electric wiring between the indoor and outdoor units
Single-phase units
Separate Power Supply for indoor unit and outdoor unit:
Outdoor Unit
Indoor Unit
1
1
L1
2 2
N1
L N
PE
Breaker
Power:220-240V~50/60Hz
L N
PE
Breaker
Power:220-240V~50/60Hz
L
N
F
C
O
L2
N2
3
1
2
24~60k
GUHD24NS3GO+GFH24S3GI/GFH24S3G1I/GKH24S3GI
. Power cord 3×2.5mm
2
(H07RN-F)
. Power cord 3×1.0mm
2
(H05RN-F)
. Communication Cords 2×0.75mm
2
(H05RN-F)
GUHD36NS3GO+GFH36S3GI/GFH36S3G1I/GKH36S3GI
GUHD42NS3GO+GFH42S3GI/GFH42S3G1I/GKH42S3GI
. Power cord 3×4.0mm
2
(H07RN-F)
. Power cord 3×1.0mm
2
(H05RN-F)
. Communication Cords 2×0.75mm
2
(H05RN-F)
GUHD48NS3GO+GFH48S3GI/GFH48S3G1I/GKH48S3GI
GUHD60NS3GO+GFH60S3GI/GFH60S3G1I
. Power cord 3×6.0mm
2
(H07RN-F)
. Power cord 3×1.0mm
2
(H05RN-F)
. CommunicationCords 2×0.75mm
2
(H05RN-F)

Table of Contents