Ultra Heat GMV Multi VRF_Heat Recovery Serial
47
01_ Set master
unit malfunction
Master unit hasn’t been set, please
set it.
Master unit is two or more than two.
Please reset.
Address DIP switch code of system
is shocking.
Master unit has been set
successfully. Next step will start
automatically.
Address allocation is finished. Next
step will start automatically.
03_Confirm the
quantity of
modules
LED3 displays the quantity of
module. In this case, please
confirm if the quantity is correct
manually.
System has confirmed the quantity
of module. Next step will start
automatically.
04_ Confirm the
quantity of IDUs
LED3 displays the quantity of IDU.
In this case, please confirm if the
quantity is correct manually.
System has confirmed the quantity
of IDU. Next step will start
automatically.
05_Internal
communication
detection
Communication between master
ODU and inverter compressor
driver has error.
Communication between master
ODU and IDUs has error.
System detection is done. Next
step will start automatically.
06_Detect
outdoor
components
System detects that outdoor
components have error.
System detects no error on outdoor
components. Next step will start
automatically.
07_Detect
indoor
components
System detects error on indoor
components. XXXX means the
project code of IDU with error. 3s
later, related error code will be
displayed.
System detects no error on indoor
components. Next step will start
automatically.
08_Confirm
preheated
compressor
LED3 displays the on-off state of
ODU valves connecting with IDU.
In this case, please confirm if the
ODU valves are open manually.
U0 means preheat time for
compressor is less than 8 hours.
Compressor has been preheated
for 8 hours. Next step will start
automatically.
System is lack of refrigerant.