Wired Controller XK55
23
Setting item Setting scope Default Remarks
Indoor unit static
pressure
1~9 5
5 selections: 3, 4, 5, 6, 7
9 selections: 1, 2, 3, 4, 5, 6, 7, 8,
9
Number of units in
group control
0:disable this function
1-16: the number of
indoor units
1
Set the number according to the
number of connected indoor
units.
Angle of return air
panel
Angle 1
Angle 2
Angle 3
Angle 1 —
Temperature of auto
mode
Auto cooling: 17
℃
~30
℃
;
Auto heating: 16
℃
~29
℃
Auto cooling:
25
℃
;
Auto heating:
20
℃
The set temperature of cooling –
the set temperature of heating
≥1
℃
Clear cleaning time Clear; Do not clear Do not clear —
Fresh air outlet
temperature
Cooling:
16
℃
~30
℃
;
Heating:
16
℃
~30
℃
Cooling:
18
℃
;
Heating:
22
℃
This function is only applicable for
fresh air indoor units.
Cold air prevention
time of indoor unit
00
:
180 seconds
01
:
300 seconds
02
:
420 seconds
03
:
600 seconds
180 seconds —
Auxiliary electric
heating function
00
:
effective under low
temperature working
condition;
01
:
effective under all
working conditions;
02
:
ineffective
Effective
under low
temperature
working
condition
—