EasyManuals Logo

Greentek SOLACE Series Installation And Operation Manual

Greentek SOLACE Series
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #3 background imageLoading...
Page #3 background image
54
INSTALLING THE OUTDOOR VENTS
INSTALLATION TYPES
Example only – duct configuration may differ depending on the model.
1. Stale air is drawn from areas requiring
local exhaust (bathroom, kitchen, laundry
room).
2. Fresh air is distributed to habitable rooms
(bedrooms, living room)
3. The HRV’s airflow must be balanced after
installation using the procedure found in
the section “AIRFLOW BALANCING.”
Suggested for:
Hydronic baseboard
In oor heating
Electric baseboard
Mini split heat pump
Benets:
Provides the best fresh air distribution in
the house; lowest operation cost since the
furnace/air handler unit is not needed.
1. The furnace blower is set to run
continuously or interconnected with HRV
for proper fresh air distribution. See
furnace electrical connection on page 12.
2. Stale air is drawn from areas requiring
local exhaust (bathroom, kitchen, laundry
room).
3. Fresh air is supplied to the return air
plenum of the furnace.
4. Due to the difference in pressure, HRV's
airflow must be balanced on site using the
procedure found in the section “AIRFLOW
BALANCING.”
* In the case of a multi-zone system, please
contact Greentek customer service prior to
installing any installation type requiring the use
of the furnace interlock
Suggested for:
Central furnace
When ducting fresh air to living area is
not possible or practical
Benets:
Conditions the fresh air prior to distributing
it throughout the house
1. The furnace blower is set to run
continuously or interconnected with HRV
for proper fresh air distribution. See
furnace electrical connection on page 12.
2. A minimum separation of 1m (39’’) is
recommended between the two direct
connections.
3. The HRV’s exhaust air connection should be
upstream of the HRV’s supply air
connection to prevent exhausting any fresh
air.
4. Due to the difference in pressure, HRV's
airflow must be balanced on site using the
procedure found in the section “AIRFLOW
BALANCING.”
* In the case of a multi-zone system, please
contact Greentek customer service prior to
installing any installation type requiring the use
of the furnace interlock"
Suggested for:
When bathroom and kitchen already have
local exhaust system
May be suitable for retrofitting
Benets:
Least expensive installation type
HRV DUCTING FOR FULLY
DEDICATED SYSTEM
HRV/FURNACE DUCTING FOR
PARTIALLY DEDICATED SYSTEM
HRV/FURNACE FOR
SIMPLIFIED INSTALLATION
BEST BETTER GOOD
Make sure the HRV is
capable of meeting the
required airow rate.
RECOMMENDED INSTALLATION
INSTALLING THE VENTS
18" 18"
(460mm)(460mm)
36" 36"
(1m)(1m)
3' 3'
(900mm)(900mm)
min.min.
36" 36"
(1m)(1m)
Intake
Should be located upstream of prevailing
winds from exhaust
At a minimum of 900 mm (3') away from
dryer vents and furnace exhaust (medium
or high efficiency furnaces), driveways, oil
fill pipes, gas meters, or garbage
containers.
Do not locate in the garage, attic, crawl
space, or underneath deck.
Locating the Exhaust Weatherhood
Not near a gas meter, electric meter or a
walkway where fog or ice could create a
hazard
Do not locate in a garage, workshop or
other unheated space
A well designed and installed ducting system will
allow the HRV to operate at its maximum
efficiency.
The inner liner of the flexible insulated duct
must be secured to the sleeve of the hood
(as close to the outside as possible) and to
the appropriate duct connection on the HRV.
The insulation should remain full and not
crushed.
1. Cut hole between wall studs
3. Secure vent with proper screws
4. Seal using outdoor rated caulking 5. Attach insulated duct from inside and tape
2. Insert vent
The outer liner, which acts as a vapor
barrier, must be completely sealed to the
outer wall and the HRV using tape and/or
caulking.
A good bead of high quality caulking
(preferably acoustical sealant) will seal the
inner flexible duct to both the HRV duct
connection and the hood prior to securing
them.
To minimize airflow restriction, the flexible
insulated duct that connects the two
outside weatherhoods to the HRV should
be stretched tightly and be as short as
possible.
Twisting or folding the duct will severely
restrict airflow.

Other manuals for Greentek SOLACE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Greentek SOLACE Series and is the answer not in the manual?

Greentek SOLACE Series Specifications

General IconGeneral
BrandGreentek
ModelSOLACE Series
CategoryVentilation Hood
LanguageEnglish