Page 15
OCF 5.0 Open Channel Flow Monitor
RELAY PARAMETERS
Relay Press and or to select a relay (2 relays are standard, 4
additional are optional).
Function Press or to select Off, Temperature, Pulse or Flow.
Temperature Air temperature at the sensor location.
Press and and set the relay On and
Off for specific temperatures.
Pulse Press and set digits to the flow volume
increment required between relay pulses.
Use this feature for remote samplers,
chlorinators or totalizers. Minimum time
between pulses is 2.25 seconds and pulse
duration is 350 milliseconds.
Flow Press to Mode and to select
Pump, Low Alarm or Hi Alarm.
Note: Function setting Flow will change according to selections made under
Units /Mode eg Level, Range, Volume or HRT.
Press to return to Menu Selections.
LOE Set relay state for ‘echo loss’ event (On, Off or Hold)
Alternate Pumps can be set to alternate when in pump mode.