- 17 -
Fig.4.5.7
Item List Parameter Input Value e.g.
10.V AC R R phase AC voltage 230.0
14.V AC S S phase AC voltage 230.0
18.V AC T T phase AC voltage 230.0
Table 4.5.1
5) Select “14.V AC S” or “18.V AC T” in Item List dropdown list and repeat above processes to
finish S phase or T phase AC voltage calibration.
7. Check the AC voltage limits via ShineBus as following steps:
1) Choose “4 Parameter” menu, select “Read” option as following figure.
Fig.4.5.8
2) Select 13, 14, 17 and 18 option in “Set ID” drop-down list, and click “Operate” button to read
the AC voltage limits in “Set value” field one by one.