- 20 -
Country Safety R1 Fac low R1 Fac high R2 Fac low R2 Fac high
Netherlands, Swiss, France VDE 0126 47.5 50.2 / /
Germany N4105 47.5 51.5 / /
UK
G83-2 47.7 51.5 47.0 52.0
G59-2 47.5 51.5 47.0 52.0
Italy CEI 0-21 47.5 51.5 49.5 50.5
Hungary Regional 49.0 51.0 / /
Barbados Regional 49.5 50.5 / /
Table 4.6.1
4. If all conditions are OK and this fault still exists, please contact Growatt service.
ANNEX
1. How to connect AC terminal (Disconnect in reverse order)
Note: There are three types of AC connector for Growatt UE series inverters. Please follow the
instructions corresponding to the parts we offer you.
A. AC connector 1:
Assembly procedure:
1) Connect the cables into their respective channels shown as Fig.5.1.1, ‘1’ represents Neutral
channel (marked with ‘1’ on the terminal), ‘2,3,4’ on Fig5.1.1 represent three Live line channels
(marked with ‘2,3,4’ on the terminal), and GND represents Ground channel (marked with
on the terminal).
Fig.5.1.1
2) Tighten the left part and right part clockwise, as Fig.5.1.2.
Fig.5.1.2
3) Connect it to the AC side of the inverter as Fig.5.13.