47
48
1.Please confirm grid is lost or not.
2.Make sure the grid connection well.
3.Make sure the breakers on grid side
are on
Output DC current too
high.
Please refer to the local
grid standard for
disconnection time
when the output DC
current is too high.
1.Restart SPA series.
2.Please contact Growatt service
center if restart can't solve the
problem.
Battery Voltage higher
than 60V.
1.Make sure the battery voltage is in
the range of specification or not.
2.Make sure the battery connection is
well
3.Check if battery is really higher
than 60V. please disconnect the
connection of battery and check
inverter.
Battery Voltage Lower
than 42 V
1.Check the real voltage of battery.
2. M a ke s ure t h e wire b e tw e e n
battery and inverter well connected.
1.Check the warning information
from lithium battery user manual.
2.Please contact Growatt service
center if restart can't solve the
problem.
1.Check the warning information
from lithium battery user manual.
2. Please contact Growatt service
center if restart can't solve the
problem.
1.Check the load of EPS. If overload
occurred at the same time, reduce
EPS load.
2. Restart inverter again.
I n t e r n a l c o m m u n i c a t i o n
failed
1.Restart SPA series.
2.Please contact Growatt service
center if restart can't solve the
problem.
1.Restart SPA series.
2.Please contact Growatt service
center if restart can't solve the
problem.
D S P a n d C O M f i r m w a r e
version
unmatch, system fault.
1.Read DSP and COM firmware
version from LCD or shinebus.
2.Check if the firmware is correct.
Inverter L N reversed or
ground
failed
1.Make sure the L line and N line is
not reversed.
2 . M a k e s u re th e P E is we l l
connected.
1.Restart SPA series.
2.Please contact Growatt service
center if restart can't solve the
problem.
Autotest failed(only in Italy)
1.Restart SPA series.
2.Please contact Growatt service
center if restart can't solve the
problem.
1.Check the load of EPS.
2. Ch ec k t h e o u t p u t o f EP S .
Especial not connect to Grid.
Please contact Growatt service
center.
Model set up not meet with
certification
Please check model set or check
the DIP setting.
Please check the temperature is in
the range of specification or not.
Table 9.1