EasyManua.ls Logo

Grundfos ALPHA2 Series - Technical Data and Installation Dimensions; Technical Data

Grundfos ALPHA2 Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
20
10. Technical data and installation dimensions
10.1 Technical data
To avoid condensation in the control box and stator, the liquid
temperature must always be higher than the ambient
temperature.
Supply voltage 1 x 230 V ± 10 %, 50/60 Hz, PE
Motor protection The pump requires no external motor protection.
Enclosure class IPX4D
Insulation class F
Relative humidity Maximum 95 % RH
System pressure Maximum 1.0 MPa, 10 bar, 102 m head
Inlet pressure
Liquid temperature Minimum inlet pressure
75 °C 0.005 MPa, 0.05 bar, 0.5 m head
90 °C 0.028 MPa, 0.28 bar, 2.8 m head
110 °C 0.108 MPa, 1.08 bar, 10.8 m head
EMC (electromagnetic
compatibility)
EMC Directive: 2004/108/EC.
Standards used: EN 55014-1:2006 and EN 55014-2:1997.
Sound pressure level The sound pressure level of the pump is lower than 43 dB(A).
Ambient temperature 0-40 °C
Temperature class TF110 to CEN 335-2-51
Surface temperature The maximum surface temperature will not exceed 125 °C.
Liquid temperature 2-110 °C
Power consumption in
manual summer mode
< 0.8 watt
Specific EEI values
ALPHAx XX-40: EEI 0.15
ALPHAx XX-50: EEI 0.16
ALPHAx XX-60: EEI 0.17
ALPHAx XX-80: EEI 0.18
ALPHAx XX-40 A: EEI 0.18
ALPHAx XX-60 A: EEI 0.20
Ambient
temperature
[°C]
Liquid temperature
Min.
[°C]
Max.
[°C]
02110
10 10 110
20 20 110
30 30 110
35 35 90
40 40 70
WARNING
Biological hazard
Death or serious personal injury.
- In domestic hot-water systems, we recommend
that you keep the liquid temperature below 65 °C
to eliminate the risk of lime precipitation. The
temperature of the pumped liquid must always be
above 50 °C due to the risk of legionella.
Recommended boiler temperature: 60 °C
If the temperature of the pumped liquid is lower than
the ambient temperature, make sure that the pump is
installed with the pump head and plug in position 6
o'clock.

Table of Contents

Related product manuals