English (GB)
9
4.3 Pump variant
IO 113 must be configured for the connected pump.
The pump type designation indicates an A, B, C or D.
Example 1, internal wiring:
SE1 80 80 40 A Ex 4 5 1D
Example 2, external wiring:
SE2.90.250.2250.4.S.496.Ex.S.5.13.C.Q.S
The letters A and C in the examples can be found on
the pump nameplate and must be referred to when
setting DIP switches 1 and 2.
Pump variant Description
PA
IO 113 without SM 113.
Sensors are connected directly to IO 113.
Position 1 ON
Position 2 OFF
PB
IO 113 with SM 113.
Sensors are connected to SM 113.
Position 1 OFF
Position 2 ON
PC
IO 113 without SM 113.
For SE/SL 9-30 kW pumps only.
Sensors are connected directly to IO 113.
Position 1 OFF
Position 2 OFF
PD
IO 113 without SM 113.
The WIO/WIA sensors are connected directly to the
pump.
Position 1 ON
Position 2 ON