4
Table1-3 Harmful gas limits in an equipment room
Gas
Max. (mg/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
NO
2
0.04
Cooling system
For adequate cooling of the firewall, follow these guidelines:
Plan the firewall installation position for the airflow direction of the firewall to match the
ventilation designs at the installation site.
Reserve a minimum clearance of 80 mm (3.15 in) around the inlet and outlet air vents.
Make sure the installation site has a good cooling system.
When installing the firewall in a standard 19-inch rack, reserve a distance of 1U (44.45 mm, or
1.75 in) between the chassis and other devices.
The F1000-AI-05 firewall cools itself naturally.
The F1000-AI-15 firewall provides front side-intake and rear side-exhaust airflow for heat dissipation.
The F1000-AI-25, F1000-AI-35, F1000-AI-55, F1000-AI-65, and F1000-AI-75 firewalls provide left
side-intake and right side-exhaust airflow for heat dissipation.
Figure1-2 Airflow through the F1000-AI-15 firewall chassis
Figure1-3 Airflow through the F1000-AI-25/F1000-AI-35/F1000-AI-55/F1000-AI-65/F1000-AI-75
firewall chassis

Table of Contents

Other manuals for H3C SecPath F50X0 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the H3C SecPath F50X0 Series and is the answer not in the manual?

H3C SecPath F50X0 Series Specifications

General IconGeneral
BrandH3C
ModelSecPath F50X0 Series
CategoryFirewall
LanguageEnglish

Related product manuals