Functions and control
Domestic air conditioner
7.1.2 The outdoor fan control (Exchange fan)
When the fan is changed among every airflow speed (including stop blowing), in order to avoid the
airflow speed from skipping frequently, it must be kept under each mode for over 30 seconds, and then
it can be changed to another mode (when cooling, the time is changed to 15 seconds).
7.1.2.1 The outdoor fan control when cooling or dehumidifying
After the compressor is started for 5 seconds, the outdoor fan is started at the medium speed at
first, after 30 seconds, it begins to control the airflow speed according to the temperature conditions of
the outdoor environment.
7.1.2.2 The outdoor fan control when heating
The temperature of the outdoor air (Ta) Airflow speed
Ta≥71.6°F
Low
66.2°F Ta<71.6°F
Keeping the speed
60.8°FTa<71.6°F
Medium
57.2°F Ta<60.8°F
Keeping the speed
Ta< 57.2°F
High
7.1.3 Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the
four-way valve.
7.1.4 Protection function
7.1.4.1 TTC high temperature-preventing protection
Once the machine is started, it can run TTC(air-blowing temp)
overheating protection of
air-blowing, but air-blowing sensor malfunction must alarm after 4 minutes during which the
compressor is started (during the course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure
run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the mean
value of the middle 2 values), take the mean value.
The temperature of the
outdoor airTa
The temperature of the outdoor
coilTe
Airflow speed
Ta≥86°F
hgiH
78.8°F Ta<86°F
—— Keeping the speed
75.2°F Ta<78.8°F
muideM
73.4°F Ta<75.2°F
—— Keeping the speed
50°FTa<73.4°F
woL
41°FTa<50°F
—— Keeping the speed
Ta<41°F 59°F Te
Low
59°F>Te
Stop
18