Functions and Control
Domestic air conditioner
7.1.3      Dehumidifying mode. 
* temperature control range: 
60.8---86 F
* temperature difference:     
30.2/33.8°F
Control feature: send the dehumidifying signal to the outdoor system. 
When Tr>Ts+35.6°F , the compressor will be turned on, the indoor fan will operate at the set speed. 
When  Tr  is  between  the  Ts  and  Ts+35.6°F ,  the  outdoor  system  will  operate  at  the  high  dehumidifying  
frequency  for  10  minutes  and  then  at  the  low  dehumidifying    mode  for  six  minutes.  The  indoor  fan  will 
operate at low speed. 
When Tr< Ts, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then turned to 
the low speed option. 
All the frequency converses have a 30.2/33.8°F  difference. 
    * Wind speed control: Automatic:   
When Tr
 Ts+41°F , high speed. 
When Ts+37.4°F Tr< Ts+41°F , medium speed. 
When Ts+35.6°F Tr< Ts+37.4°F, low speed. 
When Tr<Ts+35.6°F, light speed. 
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes. 
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system will be 
changed into light speed mode. 
When the airflow speed  has  no delay from  the high to low  switching, the speed  should  be delayed for  3 
minutes (remain at high speed for 3 minutes.) before the next switch. 
Manual: When the sensor is off or Tr< Ts+37.4°F, the manual operation can not be made. (obligatory automatic 
operation.)
*Airgate location control: the location for the airgate can be set according to your needs. 
*Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or dehumidifying). 
When the compressor works continuously for 1/6 minutes (adaptable in EEPROM) and the temperature of 
the indoor coils has been below zero centigrade for 10 seconds, the compressor will be stopped and the 
malfunction  will  be  recorded  in  the  malfunction  list.  The  indoor  system  will  continue  to  run.  When  the 
temperature of the indoor coil is raised to 44.6°F, the compressor will be restarted again (the requirement of 3 
minutes’ delay should be satisfied.) 
* Coil protection (synchronic overheating protection) are installed for the four directions latch malfunctions 
when dehumidifying. 
* Timing system on/off function. 
* Dormant control functio
n.
7.1.4      Heating operation mode. 
*
temperature control range: 60.8---86 F
* temperature difference:   30.2/33.8°F   
* control feature: the temperature compensation is automatically added and the system will send the heating 
signals to the outdoor system. 
If Tr
Ts, the outdoor compressor is turned on, the indoor fan will be at the cold air proof mode. 
If Tr>Ts+35.6°F, the outdoor system is turned off, the indoor fan will be at the heat residue sending mode. 
If Tr<Ts+35.6°F, the outdoor system will be turned on again, the indoor fan will be at the cold air proof mode. 
15
<
<