Functions and control
 
                                                                                                                                           
Domestic air conditioner 
During the starting process of the compressor, if the AC current is greater than 7A, the frequency of 
the compressor increases at the prohibited speed.   
During the starting process of the compressor, if the AC current is greater than 6.5A, the frequency of 
the compressor increases at the speed of no faster than 0.1HZ/second.   
 
7.1.4.4 The protection function of AC current: 
During the starting process of the compressor, if the AC current is greater than 12A for 3 seconds, 
stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3 times in 20 
minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to run it only 
after the the power is off. 
During the starting process of the compr
essor, if the AC current is greater than 9A, the frequency of 
the compressor decreases at the speed of 1HZ/second.   
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of 
the compressor decreases at the speed of 0.1HZ/second.   
During the starting process of the compressor, if the AC current is greater than 7A, the frequency of 
the compressor increases at the prohibited speed.   
During the starting process of the compressor, if the AC current is greater than 6.5A, the frequency of 
the compressor increases at the speed of no faster than 0.1HZ/second.   
Remarks: when the outdoor temperature is high, there’s compensation for AC current protectio
n.   
(1)  When  the  outdoor  environment  temperature  is  higher  than  104°F,  AC  current  protection  value 
decreases by 1A. 
(2)  When  the  outdoor  environment  temperature  is  higher  than122°F,  AC  current  protection  value 
decreases by 2.5A. 
 
7.1.4.5 Anti-freezing protection of the indoor heat exchanger 
When cooling/heating, prevent freezing. 
Tpg_indoor is the minimum value of the effective indoor unit (start it and it is in accord with the running 
state). 
 
                       
                                             51.8°F //ice_temp_3+5 
ice_temp_3+3      48.2°F                                                                           
                                                                                          Increasing slowly 
                                                                               
              46.4°F //ice_temp_3+2 
                                                                        Keeping the frequency 
ice_temp_3          44.6°F                                                          44.6°F 
ice_temp_2          41°F                                                   Decreasing slowly 
ice_temp_1          °F                                                   Decreasing rapidly    ice_temp_1 
                32°F                                                   Stop 
 
When  Tpg_indoor〈  ice_temp_33.8°F,  the  frequency  of  the  compressor  decreases  at  the  speed  of 
1HZ/1second. 
When  Tpg_indoor〈  ice_temp_35.6°F ,  the  frequency  of  the  compressor  decreases  at  the  speed  of 
1HZ/10seconds.   
When Tpg_indoor begi
ns to rise again, and ice_temp_2≤Tpg_indoor≤  ice_temp_37.4°F, the frequency 
of the compressor doesn’t change.   
20
37.4