SEQUENCE OF OPERATION
PAGE 23
ENGLISH
The outdoor unit main board also controls the position of 
the EEV (Electronic Expansion Valve) to regulate the ow of 
refrigerant to the indoor unit evaporator coil.    
 
Temperature Sensors
 
Four temperature sensors located in the outdoor unit provide 
temperature information to the outdoor unit main board for 
control of the system during cool mode.
The outdoor ambient temperature sensor provides the tem-
perature of the air drawn into the outdoor coil of the outdoor 
unit.
The defrost temperature sensor provides the temperature 
sensed at the output of the outdoor coil.
The suction line temperature sensor provides the tempera-
ture sensed at the incoming suction line pipe.
The compressor discharge sensor provides the temperature 
sensed at the discharge pipe of the compressor.
 
Call to Terminate Cooling
 
The system will call to terminate cooling when the indoor am-
bient temperature sensor is equal to or lower than 2°F of the 
room set temperature. The indoor control board will com-
municate to the outdoor control board to de-energize the 
compressor. The outdoor fan will run for 60 seconds before 
stopping.
The indoor fan motor and louver will continue operating after 
cooling has been terminated.
To stop cool mode, press the power button to turn the sys-
tem o, or change to another mode.
 
Freeze Protection Function
 
To prevent freezing of the indoor unit coil during cool mode, 
when the compressor operates continuously for 10 seconds 
and the temperature of the indoor coil has been below 32°F 
for 10 seconds, the compressor will stop, and the error will 
be recorded in the malfunction list. The indoor unit fan will 
continue to operate. When the temperature of the indoor coil 
rises to 45°F for more than 3 minutes  the compressor will 
restart and the system will continue functioning.
Heat Mode
 
Overview
 
The setpoint control range in heating mode is 60°F - 86°F. The 
temperature set by the remote control and the indoor unit 
ambient temperature sensor will determine if a call for heat is 
needed. If a call for heat is justied, a temperature compen-
sation adjustment is automatically added to the operating 
parameter and the call is communicated from the indoor unit 
to the outdoor unit.
The indoor unit louver will open using a stepper motor. The 
indoor fan will not operate at this time. 
The outdoor unit will shift the 4-way valve to the heat mode 
position and determine the position of the EEV (if equipped) 
and speed (frequency) of the compressor. There can be a 
delay of up to 3 minutes before the outdoor unit fan and com
-
pressor start.
(Tr = room temperature  Ts = set temperature)
If  Tr ≤ Ts, the outdoor unit will operate and the indoor fan 
operates in cold air prevention function
If Tr > Ts+, the outdoor unit turns o and the indoor fan oper-
ates at heat residue sending mode.
If Tr < Ts+, the outdoor unit will restart and the indoor fan 
operates in cold air proof mode.   
The speed of the indoor fan can be controlled manually by 
the user or automatically by the system. The speed can be 
changed between HIGH, MEDIUM, and LOW. The predeter-
mined conditions for automatic control are as follows:
High Speed: Tr < Ts
Medium Speed: Ts ≤ Tr ≤ Ts + 4°F
Low Speed: Tr > Ts + 4°F
When the indoor fan is running in automatic mode and there 
is no delay when the speed switches from high to low, the 
indoor fan will maintain high speed for a period of 3 minutes 
before switching  to low speed.
 
Cold Air Proof Operation 
 
At initial start of heat mode, indoor blower will not be turned 
on immediately until indoor coil temperature senses a mini-
mum temperature. This period usually takes 30 seconds to 3 
minutes depending on the outdoor ambient temperature.   
                                                                      HSU12HG(DB)-SM                                          Wiring Diagrams
16 
Domestic Air Conditioner
        *Indoor fan control 
    manual control: You can choose high, medium, low and automatic speed control. 
    Automatic: When Tr<Ts, high speed. 
                        When Ts≤Tr≤Ts+2ć, medium speed. 
                        When Tr> Ts+2ć, low speed. 
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 
3 minutes (remain at high speed for 3 minutes.) before the next switch. 
*Airgate location control: the location for the airgate can be set according to your needs. 
Coldair proof operation 
1. The indoor operation within 4 minutes after the start up is as the following diagram, the air speed 
can be raised only after the speed has reached a certain level. 
2. 4 minutes after the start up of the indoor fan, the light airflow and the low airflow will be turned to the 
set speed airflow. 
3. In the cold air proof operation, the fan won’t stop after the start up. 
4. During the cold air  proof operation, the indoor system will continuously send ‘indoor  high speed’ 
signals to the outdoor system. 
* Residue heat sending. The indoor fan will send the residue heat at a low speed for 12 seconds. 
If other conditions are satisified, when the compressor stops, the indoor system will operate at a light 
speed. The indoor fan will stop when the coil temperature is below the ‘heat start temp 4’. 
* Defrosting. When the system receives the defrosting signal from outdoors, the indoor fan will stop 
and  the  indoor  temperature  display  won’t change.  At  the  time,  any indoor  coil  malfunctions  will  be 
neglected. When the outdoor defrosting finishes, the coil malfunction will still be neglected  until the 
compressor has been started up for 30 seconds. The indoor temperature display will not change and 
the system operates at the cold air proof mode. 
*  Automatic  heating  temperature  compensation:  when  the  system  enters  the  heating  mode,  the 
temperature compensation (4) will be added. When the status is switched off, the compensation will 
be erased. 
 
 
 
 
 
 
 
 
 
Heat start temp 1 
Heat start temp
 2 
Heat start temp
 3 
Heat start temp
 4 
Low speed
Light speed 
Fan/off 
Fan/off 
Keep  the  hig
speed. The fa
doesn’t stop
4 minutes after the indoor fan starts, the light or low speed 
will switch to the set speed.
In cold air proof operation, the fan remains on after startup.
Residual heat sending: The indoor fan will operate on low 
speed for 12 seconds.  
Outdoor unit temperature sensors: Outdoor ambient, 
defrost, suction line, and compressor discharge, used in 
conjunction with the indoor temperature sensors, indoor 
ambient and tube, provide information to the outdoor control 
board to monitor the system and regulate the frequency of 
the compressor, EEV positioning, and outdoor fan speed to 
achieve the desired room temperature.