47
If sensor terminal is xed well
If voltage between red terminal
and black terminal is 5V when
testing pressure sensor by
multimeter
If voltage between white terminal and black
terminal is 0.5V~3.5V when testing pressure
sensor by multimeter
Replace connecting board
Reconnect
Replace PCB
Replace pressure sensor
No
No
No
Yes
Yes
Yes
[28, 29] High/low pressure sensor failure