6
Model  AU04IFPERA AU05IFPERA AU06IFPERA
Power supply Ph/V/Hz 3N,380-400V,50/60Hz
Outdoor 
fan
Brand  Haier Haier Haier
Model  / / /
Material Plastic Plastic Plastic
Type Axial Axial Axial
Diameter mm 550 550 550
Height mm 200 200 200
Outdoor 
coil
Number of rows 2 2 2
Tube pitch(a)x row pitch(b)   mm 21*18.186 21*18.186 21*18.186
Fin spacing                 mm 1.4 1.4 1.4
Fin type (code) Hydrophilic aluminium 
Fin Coating Type Optional Clear lacquer Clear lacquer Clear lacquer
Salt Spray Test Duration  Hour 168 168 168
Tube outside dia. and type 
Inner groove tube
mm Ф7 Ф7 Ф7
Coil length x height  mm 1077*1315 1077*1315 1077*1315
Number of circuits 7 7 7
Cabinet 
coating
Coating type  Powder coating Powder coating Powder coating
Salt Spray Test Duration  Hour 72 72 72
Sheet Metal Material Hot zinc plate Hot zinc plate Hot zinc plate
Sheet Metal Thickness mm 0.8 0.8 0.8
Control panel enclosure IP class Standard IP24 IP24 IP24
Outdoor air ow             m
3
/h 7200 7200 7200
Outdoor sound level(sound pressure level) dB(A) 50 51 53
Outdoor sound level(sound power level) dB(A) 68 69 70
Outdoor 
unit
Dimension(W*H*D) mm 950/370/1340 950/370/1340 950/370/1340
Packing  (W*H*D) mm 1023/471/1420 1023/471/1420 1023/471/1420
Net weight   kg 115 115 115
Gross weight   kg 123 123 123
Refrigerant 
Type R410A R410A R410A
Charged volume kg 4 4 4
Throttle type EXV EXV EXV
Design pressure              MPa 4.15 4.15 4.15
Refrigerant 
piping
Liquid pipe mm 9.52 9.52 9.52
Gas pipe mm 15.88 15.88 15.88
Total pipe length m 300 300 300
Max. pipe length(Equivalent/ 
Actual)
m 175/150 175/150 175/150
Max. Diff. indoor/outdoor unit m
50 (Outdoor higher than indoor)
40 (Indoor higher than outdoor)
Max. Diff. indoor/indoor unit m 15 15 15
Connectable indoor unit ratio % 50%~130% 50%~130% 50%~130%
Maximum indoor units Piece 8 10 13
Connection 
wiring
Power wiring mm
2
4 4 4
Signal wiring mm
2
Shield wire:(0.75-2)*2
Operation Range                °C
Cooling:-15~48 
Heating:-20~27
Norminal condition: indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating):
20°CDB/14.5°C WB.
Outdoor temperature(cooling): 35°C DB/24°C WB, outdoor temperature(heating): 7°C DB/6°C WB The data is 
measured with 7.5m equivalent pipe and 0 m height difference.
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a 
Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.